Air cooled chiller 26-48 kw

R410A refrigerant gas Chillers and heat pumps are designed to meet the cooling needs of small and medium-sized residential and office buildings. All units have class A energy efficiency and are equipped with inverter control on the Scroll compressor to provide higher efficiency at part loads (SEER/IPLV/SCOP). The following versions of these units are available.

  • CHA/IK/A - Cooling only
  • CHA/IK/A/MC - Cooling only with microchannel condensing coil
  • CHA/IK/A/WP - Both heating and cooling
Chillers with microchannel condensing coil provide high efficiency (high EER) due to better heat exchange than traditional coil chillers. 
The units comply with the ErP Regulation. Upon request, the devices can be equipped with R452B or R454B refrigerant gas.

Features
  • Corrosion-resistant supporting frame construction made of Peraluman and galvanized metal
  • Soundproof compressor compartment
  • Inverter DC Scroll Compressor with oil sight glass, internal heat protection, crankcase heater and soundproofing cover
  • Axial fans connected to single-head external rotor motors with low ventilation and special blade profile
  • Copper tube and aluminum blade condenser made of coils or aluminum microchannel coils
  • The evaporator is made of AISI 316 stainless steel and brazed plate type and is equipped with a water differential pressure switch.
  • Antifreeze heater in heat pump units
  • Electronic expansion valve
  • R410A refrigerant gas, optionally R452B or R454B refrigerant
  • Microprocessor control and regulation system

Technical Specifications
  



91101131151
Cooling STD versionsCooling capacity (1)kW25,830,535,942,3
Input power (1)kW8,09,511,313,4
EER (1)
3,223,213,183,16
Cooling STD versions (EN14511)Cooling capacity (1)kW25,730,435,842,2
Input power (1)kW8,19,611,413,6
EER (1)
3,193,163,133,11
SEER (2)
4,424,164,214,22
Energy efficiency (2)%174163165166
Cooling MC versionsCooling capacity (1)kW25,830,535,942,3
Input power (1)kW7,99,411,213,3
EER (1)
3,273,243,213,18
Cooling MC versions (EN14511)Cooling capacity (1)kW25,730,435,842,2
Input power (1)kW8,09,511,313,5
EER (1)
3,233,203,163,13
SEER (2)
4,484,214,264,27
Energy efficiency (2)%176165167168
Heating STD versionsHeating capacity (3)kW28,734,340,448,0
Input power (3)kW8,19,911,814,0
COP (3)
3,543,463,423,43
Heating STD versions (EN14511)Heating capacity (3)kW28,834,440,548,1
Input power (3)kW8,210,112,014,2
COP (3)
3,513,423,373,38
SCOP (4)
3,743,753,543,74
Energy efficiency (4)%147147139147
Energy class (5)
A+A+A+A+
SCOP (6)
2,952,962,933,07
Energy efficiency (6)%115115114120
Energy class (7)
A+A+A+A+
CompressorQuantity1111
EvaporatorWater flow ratel/s1,231,461,712,02
Pressure dropkPa20293131
Water connections"G1 ¼"1 ¼"1 ¼"1 ¼"
Electrical characteristicsPower supplyV/Ph/Hz400/3+N/50400/3+N/50400/3+N/50400/3+N/50
Max. running currentA21242734
Max. starting currentA11141518
Pump-equipped unitsAvailable pump headkPa140115150105
Water connections"G1 ¼"1 ¼"1 ¼"1 ¼"
Sound levelSTD versions (8)dB(A)6061

Dimensions
 



91101131151
LengthSTD/MCmm1850185018501850
WidthSTD/MCmm1000100010001000
HeightSTD/MCmm1300130013001300

Notes

 1.  Chilled water 12 °C → 7 °C, ambient air 35 °C.
2.  Seasonal energy efficiency for cooling at low temperature (EU Reg. No. 2016/2281).
3.  Heated water 40 °C → 45 °C, ambient air 7 °C D.B./6 °C W.B.
4.  Seasonal energy efficiency for heating at low temperature, average climate (EU Reg. No. 813/2013).
5.  Seasonal efficiency class for heating at low temperature (EU Reg. No. 811/2013).
6.  Seasonal energy efficiency for heating at medium temperature (EU Reg. No. 813/2013).
7.  Seasonal efficiency class for heating at medium temperature (EU Reg. No. 811/2013).
 8.  Sound-pressure level measured at 1 m from the unit in free-field conditions (ISO 3744).